In order to better improve the stability of protection, the minimum switching current of the fuse cannot exceed the minimum junction current, and the minimum switching current of the fuse should be as small as possible. The current below the minimum power switching current of the fuse shall be interrupted by the vacuum contactor. When the current of the fuse is less than the minimum power switching current of the fuse, the high quality arc withstand force of the fuse should be longer than that of the cooperative vacuum contactor.
When protecting power engineering loads, for motor loads, the blocking current of the motor should be within the switching current of the vacuum contactor, the fuse cannot be switched, and the operating current of the motor or the duration of the sudden investment current should be within the minimum performance characteristics of the comprehensive protection device The following, to prevent misoperation of the vacuum contactor.
For the transformer load, when the fault on the bottom voltage side of the transformer or the internal structure of the transformer is moved by the vacuum contactor, the fuse should be able to protect the short circuit fault on the bottom voltage side of the transformer, and the minimum switching current of the fuse should be less than the preset Estimated short-circuit fault current.
When the electrical control system of the processing plant is equipped with grounding device power-off protection, attention should be paid to the neutral point grounding method and the selection of neutral point grounding equipment to prevent the vacuum contactor from being powered off when the current exceeds the rated value of the vacuum contactor to break the current. The actual selection method can refer to DL/T5153 "Technical Regulations for Power Design of Thermal Power Plants".
When cooperating with left and right switching power supply protection, in order to ensure the selectivity of F-C power supply circuit protection, the behavioral characteristics of the isolating switch comprehensive protection device on the switching power supply side should be on the right side of the current characteristic curve, and the behavioral characteristics of the equipment protection device on the load side It should be on the left side of the current characteristic curve.
Overload protection. The long-term overload of the motor power circuit will cause the motor stator to overheat, resulting in aging of the motor insulation, and even motor damage or serious short-circuit failure. Fuse overload protection is one of the key protections of the motor power circuit, which reflects the overload level of the motor.
When the motor is overloaded, because the circuit current is small, the vacuum contactor is usually taken into consideration for protection.
The operation time of the overload protection should be consistent with the allowable overload time of the motor. In general, the power-on time of the motor is longer.
The overload protection given by the comprehensive protection equipment is inverse period protection, and the curve changes with the steady state value of heating and the change of cold and hot operation. When selecting the curve, in addition to the specific heating parameters and operating conditions of the motor, it should be prevented that the motor runs and the current value matching the intersection point of the selected curve and the fuse characteristic curve is lower than the rated value of the AC contactor. current.
Taking the calculation method brought by the comprehensive protection equipment manufacturer as an example, the calculation method of the over-temperature protection heating steady-state value (T1) is given to prevent running current.
The intersection with the time-length-current characteristic curve F of the fuse is P, and the matching current value I is lower than the overcurrent locking current value of the comprehensive protection equipment specified by the breaking current of the rated value of the AC contactor.
If the protection of the F-C power supply circuit is composed of curves R and F, when the common fault current exceeds I, the fuse blows and cuts off the power circuit; when the current is lower than IP and exceeds I, the comprehensive protection device bypasses the AC contactor. If the fuse marks the overcurrent locking current value N point of the comprehensive protection device on the fuse time curve, when the fault current is within the range of I~IN, the AC contactor is fully capable of cutting off the circuit.